Wiring 2 or 3 outlets controlled by one switch










3















I want 2 ( maybe 3) outlets controlled by the same switch. Easy enough. But, in addition, I want half of each outlet controlled by the switch and the other half of each outlet always hot. Is there a wiring diagram somewhere for this? I just haven't found it. A diagram would help confirm how I think it should be done. They will be in the same room and the wiring will be relatively easy to run.










share|improve this question



















  • 1





    The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

    – Glen Yates
    Nov 14 '18 at 16:57






  • 1





    @GlenYates then it's kinda the next owner's issue to fix, isn't it?

    – FreeMan
    Nov 14 '18 at 20:56






  • 2





    @GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

    – R..
    Nov 14 '18 at 21:34







  • 1





    It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

    – CactusCake
    Nov 14 '18 at 22:02






  • 1





    It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

    – Glen Yates
    Nov 14 '18 at 23:00















3















I want 2 ( maybe 3) outlets controlled by the same switch. Easy enough. But, in addition, I want half of each outlet controlled by the switch and the other half of each outlet always hot. Is there a wiring diagram somewhere for this? I just haven't found it. A diagram would help confirm how I think it should be done. They will be in the same room and the wiring will be relatively easy to run.










share|improve this question



















  • 1





    The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

    – Glen Yates
    Nov 14 '18 at 16:57






  • 1





    @GlenYates then it's kinda the next owner's issue to fix, isn't it?

    – FreeMan
    Nov 14 '18 at 20:56






  • 2





    @GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

    – R..
    Nov 14 '18 at 21:34







  • 1





    It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

    – CactusCake
    Nov 14 '18 at 22:02






  • 1





    It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

    – Glen Yates
    Nov 14 '18 at 23:00













3












3








3








I want 2 ( maybe 3) outlets controlled by the same switch. Easy enough. But, in addition, I want half of each outlet controlled by the switch and the other half of each outlet always hot. Is there a wiring diagram somewhere for this? I just haven't found it. A diagram would help confirm how I think it should be done. They will be in the same room and the wiring will be relatively easy to run.










share|improve this question
















I want 2 ( maybe 3) outlets controlled by the same switch. Easy enough. But, in addition, I want half of each outlet controlled by the switch and the other half of each outlet always hot. Is there a wiring diagram somewhere for this? I just haven't found it. A diagram would help confirm how I think it should be done. They will be in the same room and the wiring will be relatively easy to run.







switch receptacle wire






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited Nov 14 '18 at 21:48







KCB3rd

















asked Nov 14 '18 at 4:49









KCB3rdKCB3rd

346




346







  • 1





    The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

    – Glen Yates
    Nov 14 '18 at 16:57






  • 1





    @GlenYates then it's kinda the next owner's issue to fix, isn't it?

    – FreeMan
    Nov 14 '18 at 20:56






  • 2





    @GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

    – R..
    Nov 14 '18 at 21:34







  • 1





    It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

    – CactusCake
    Nov 14 '18 at 22:02






  • 1





    It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

    – Glen Yates
    Nov 14 '18 at 23:00












  • 1





    The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

    – Glen Yates
    Nov 14 '18 at 16:57






  • 1





    @GlenYates then it's kinda the next owner's issue to fix, isn't it?

    – FreeMan
    Nov 14 '18 at 20:56






  • 2





    @GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

    – R..
    Nov 14 '18 at 21:34







  • 1





    It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

    – CactusCake
    Nov 14 '18 at 22:02






  • 1





    It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

    – Glen Yates
    Nov 14 '18 at 23:00







1




1





The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

– Glen Yates
Nov 14 '18 at 16:57





The next owner will probably not be happy about this. Assuming this is for controlling plug-in lamps, with all the 'smart' products coming out now, is it really necessary?

– Glen Yates
Nov 14 '18 at 16:57




1




1





@GlenYates then it's kinda the next owner's issue to fix, isn't it?

– FreeMan
Nov 14 '18 at 20:56





@GlenYates then it's kinda the next owner's issue to fix, isn't it?

– FreeMan
Nov 14 '18 at 20:56




2




2





@GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

– R..
Nov 14 '18 at 21:34






@GlenYates: Said "smart" products are junk, and probably will be for the forseeable future, because there's no incentive to make non-awful. But just a traditional plug-in xmas-tree-remote system would be a lot less awful and more obvious to the user what's going on than having half the outlet mysteriously on a switch with the logic hidden inside the walls.

– R..
Nov 14 '18 at 21:34





1




1





It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

– CactusCake
Nov 14 '18 at 22:02





It's really not that hard for the next owner to revert if they don't like it. You just cap off the switched hot in each box and either pigtail both hot terminals to the remaining hot, or replace with a new outlet that still has the tab in place (outlets are dirt cheap). Shouldn't take more than 5 minutes per box.

– CactusCake
Nov 14 '18 at 22:02




1




1





It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

– Glen Yates
Nov 14 '18 at 23:00





It is KCB3rd's house, so he can do what he wants with it, I really just wanted to point out that there may be alternatives. One that's been around for a long time is an X10 controller, this would provide flexibility to move the controlled outlet at will.

– Glen Yates
Nov 14 '18 at 23:00










2 Answers
2






active

oldest

votes


















20














Wiring diagram, though I hope you don't really need it:



switched outlet halves



Don't forget to break the tabs off the hot side of the outlets.






share|improve this answer


















  • 7





    +1 for hand drawn red ---circles--- wires

    – FreeMan
    Nov 14 '18 at 14:17






  • 2





    +1 for diagram.

    – J. Chris Compton
    Nov 14 '18 at 15:42






  • 4





    I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

    – KCB3rd
    Nov 14 '18 at 17:38


















6














The switch opens or closes contact on the hot wire leading to the outlet(s) (receptacles) that you want to control with it. It "makes or breaks" the hot connection to the load. An additional unswitched hot wire would need to run to the receptacles that will not be controlled by the switch.



So... you will need a run of wires that includes a switched hot, an unswitched hot, a neutral, and a ground wire. If you plan on using NM sheathed cable (e.g. Romex) you would need 3 conductor w/ground, e.g. 12-3 w/ground.



If you plan on using common duplex receptacles (the devices with 2 "outlets" on a single frame), you will need to break off a little jumper tab that ties the wire contact plate under the terminal screws together on the hot side, to isolate the switched receptacle from the unswitched.



No diagram is really needed because if this does not make sense to you then you ought to hire an electrician.






share|improve this answer


















  • 3





    +1 "if this does not make sense... you ought to hire an electrician"

    – J. Chris Compton
    Nov 14 '18 at 15:39






  • 1





    You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

    – J...
    Nov 14 '18 at 23:37






  • 1





    14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

    – Timbo
    Nov 15 '18 at 1:23










Your Answer








StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "73"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);

else
createEditor();

);

function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);



);













draft saved

draft discarded


















StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150568%2fwiring-2-or-3-outlets-controlled-by-one-switch%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown

























2 Answers
2






active

oldest

votes








2 Answers
2






active

oldest

votes









active

oldest

votes






active

oldest

votes









20














Wiring diagram, though I hope you don't really need it:



switched outlet halves



Don't forget to break the tabs off the hot side of the outlets.






share|improve this answer


















  • 7





    +1 for hand drawn red ---circles--- wires

    – FreeMan
    Nov 14 '18 at 14:17






  • 2





    +1 for diagram.

    – J. Chris Compton
    Nov 14 '18 at 15:42






  • 4





    I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

    – KCB3rd
    Nov 14 '18 at 17:38















20














Wiring diagram, though I hope you don't really need it:



switched outlet halves



Don't forget to break the tabs off the hot side of the outlets.






share|improve this answer


















  • 7





    +1 for hand drawn red ---circles--- wires

    – FreeMan
    Nov 14 '18 at 14:17






  • 2





    +1 for diagram.

    – J. Chris Compton
    Nov 14 '18 at 15:42






  • 4





    I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

    – KCB3rd
    Nov 14 '18 at 17:38













20












20








20







Wiring diagram, though I hope you don't really need it:



switched outlet halves



Don't forget to break the tabs off the hot side of the outlets.






share|improve this answer













Wiring diagram, though I hope you don't really need it:



switched outlet halves



Don't forget to break the tabs off the hot side of the outlets.







share|improve this answer












share|improve this answer



share|improve this answer










answered Nov 14 '18 at 6:22









A. I. BreveleriA. I. Breveleri

7,2721823




7,2721823







  • 7





    +1 for hand drawn red ---circles--- wires

    – FreeMan
    Nov 14 '18 at 14:17






  • 2





    +1 for diagram.

    – J. Chris Compton
    Nov 14 '18 at 15:42






  • 4





    I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

    – KCB3rd
    Nov 14 '18 at 17:38












  • 7





    +1 for hand drawn red ---circles--- wires

    – FreeMan
    Nov 14 '18 at 14:17






  • 2





    +1 for diagram.

    – J. Chris Compton
    Nov 14 '18 at 15:42






  • 4





    I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

    – KCB3rd
    Nov 14 '18 at 17:38







7




7





+1 for hand drawn red ---circles--- wires

– FreeMan
Nov 14 '18 at 14:17





+1 for hand drawn red ---circles--- wires

– FreeMan
Nov 14 '18 at 14:17




2




2





+1 for diagram.

– J. Chris Compton
Nov 14 '18 at 15:42





+1 for diagram.

– J. Chris Compton
Nov 14 '18 at 15:42




4




4





I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

– KCB3rd
Nov 14 '18 at 17:38





I'll use my 12-3 indoor wire. I kinda thought it would be as the diagram showed, just good to see a diagram for visual confirmation.

– KCB3rd
Nov 14 '18 at 17:38













6














The switch opens or closes contact on the hot wire leading to the outlet(s) (receptacles) that you want to control with it. It "makes or breaks" the hot connection to the load. An additional unswitched hot wire would need to run to the receptacles that will not be controlled by the switch.



So... you will need a run of wires that includes a switched hot, an unswitched hot, a neutral, and a ground wire. If you plan on using NM sheathed cable (e.g. Romex) you would need 3 conductor w/ground, e.g. 12-3 w/ground.



If you plan on using common duplex receptacles (the devices with 2 "outlets" on a single frame), you will need to break off a little jumper tab that ties the wire contact plate under the terminal screws together on the hot side, to isolate the switched receptacle from the unswitched.



No diagram is really needed because if this does not make sense to you then you ought to hire an electrician.






share|improve this answer


















  • 3





    +1 "if this does not make sense... you ought to hire an electrician"

    – J. Chris Compton
    Nov 14 '18 at 15:39






  • 1





    You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

    – J...
    Nov 14 '18 at 23:37






  • 1





    14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

    – Timbo
    Nov 15 '18 at 1:23















6














The switch opens or closes contact on the hot wire leading to the outlet(s) (receptacles) that you want to control with it. It "makes or breaks" the hot connection to the load. An additional unswitched hot wire would need to run to the receptacles that will not be controlled by the switch.



So... you will need a run of wires that includes a switched hot, an unswitched hot, a neutral, and a ground wire. If you plan on using NM sheathed cable (e.g. Romex) you would need 3 conductor w/ground, e.g. 12-3 w/ground.



If you plan on using common duplex receptacles (the devices with 2 "outlets" on a single frame), you will need to break off a little jumper tab that ties the wire contact plate under the terminal screws together on the hot side, to isolate the switched receptacle from the unswitched.



No diagram is really needed because if this does not make sense to you then you ought to hire an electrician.






share|improve this answer


















  • 3





    +1 "if this does not make sense... you ought to hire an electrician"

    – J. Chris Compton
    Nov 14 '18 at 15:39






  • 1





    You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

    – J...
    Nov 14 '18 at 23:37






  • 1





    14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

    – Timbo
    Nov 15 '18 at 1:23













6












6








6







The switch opens or closes contact on the hot wire leading to the outlet(s) (receptacles) that you want to control with it. It "makes or breaks" the hot connection to the load. An additional unswitched hot wire would need to run to the receptacles that will not be controlled by the switch.



So... you will need a run of wires that includes a switched hot, an unswitched hot, a neutral, and a ground wire. If you plan on using NM sheathed cable (e.g. Romex) you would need 3 conductor w/ground, e.g. 12-3 w/ground.



If you plan on using common duplex receptacles (the devices with 2 "outlets" on a single frame), you will need to break off a little jumper tab that ties the wire contact plate under the terminal screws together on the hot side, to isolate the switched receptacle from the unswitched.



No diagram is really needed because if this does not make sense to you then you ought to hire an electrician.






share|improve this answer













The switch opens or closes contact on the hot wire leading to the outlet(s) (receptacles) that you want to control with it. It "makes or breaks" the hot connection to the load. An additional unswitched hot wire would need to run to the receptacles that will not be controlled by the switch.



So... you will need a run of wires that includes a switched hot, an unswitched hot, a neutral, and a ground wire. If you plan on using NM sheathed cable (e.g. Romex) you would need 3 conductor w/ground, e.g. 12-3 w/ground.



If you plan on using common duplex receptacles (the devices with 2 "outlets" on a single frame), you will need to break off a little jumper tab that ties the wire contact plate under the terminal screws together on the hot side, to isolate the switched receptacle from the unswitched.



No diagram is really needed because if this does not make sense to you then you ought to hire an electrician.







share|improve this answer












share|improve this answer



share|improve this answer










answered Nov 14 '18 at 5:45









Jimmy Fix-itJimmy Fix-it

20.9k1129




20.9k1129







  • 3





    +1 "if this does not make sense... you ought to hire an electrician"

    – J. Chris Compton
    Nov 14 '18 at 15:39






  • 1





    You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

    – J...
    Nov 14 '18 at 23:37






  • 1





    14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

    – Timbo
    Nov 15 '18 at 1:23












  • 3





    +1 "if this does not make sense... you ought to hire an electrician"

    – J. Chris Compton
    Nov 14 '18 at 15:39






  • 1





    You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

    – J...
    Nov 14 '18 at 23:37






  • 1





    14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

    – Timbo
    Nov 15 '18 at 1:23







3




3





+1 "if this does not make sense... you ought to hire an electrician"

– J. Chris Compton
Nov 14 '18 at 15:39





+1 "if this does not make sense... you ought to hire an electrician"

– J. Chris Compton
Nov 14 '18 at 15:39




1




1





You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

– J...
Nov 14 '18 at 23:37





You'd only need 12/3 copper if this is a 20A circuit. Most branch circuits will be 15A, so 14/3 is most likely the correct wire.

– J...
Nov 14 '18 at 23:37




1




1





14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

– Timbo
Nov 15 '18 at 1:23





14/3 is most likely the correct minimum but 12 is allowed and arguably better in all aspects except cost and difficulty of fishing.

– Timbo
Nov 15 '18 at 1:23

















draft saved

draft discarded
















































Thanks for contributing an answer to Home Improvement Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid


  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.

To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f150568%2fwiring-2-or-3-outlets-controlled-by-one-switch%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







這個網誌中的熱門文章

Barbados

How to read a connectionString WITH PROVIDER in .NET Core?

Node.js Script on GitHub Pages or Amazon S3